FLUKE 435 POWER QUALITY
Pinpoint power quality problems faster, safer and in greater detail with the Fluke 435 power quality analyzer. These three-phase power quality meters help you locate, predict, prevent and troubleshoot problems in power distribution systems. These easy-to-use power quality tools are a “must have ” for any person who maintains or troubleshoots three phase power. The new IEC Class A standards for flicker and power quality are built right in to take the guess work out of power monitoring.
Features:
\r
Automatic transient mode: Captures 200 kHz waveform data on all phases simultaneously: Up to 6 kV\r
Highest safety rating in the industry: 600 V Cat IV/1000 V CAT III rated for use at the service entrance\r
Troubleshoot real-time: Analyze the trends using the cursors and zoom tools even while background recording continues
Applications:
\r
Automatic transient mode: Captures 200 kHz waveform data on all phases simultaneously: Up to 6 kV\r
Highest safety rating in the industry: 600 V Cat IV/1000 V CAT III rated for use at the service entrance\r
Troubleshoot real-time: Analyze the trends using the cursors and zoom tools even while background recording continues
Volt/Amps/Hertz | Vrms (AC + DC) Measurement range: 1 ... 1000 V Accuracy: 0.1% of Vnom Vpeak Measurement range: 1 ... 1400 V Accuracy: 5% of Vnom Crest factor voltage Measurement range: 1.0 ... > 2.8 Accuracy: ±5% Arms (AC + DC) |
Inputs | Number: 4 voltage and current (3 phases + neutral) Maximum voltage: 1000 Vrms (6 kV peak) |
Dips and swells | Vrms (AC+DC) ² Measurement range: 0.0% & 100% of Vnom Accuracy: ±0.2% of nominal voltage Arms (AC+DC) ² |
Harmonics | Measurement range: DC 1..50; (Off 1..49) Vrms Measurement range: 0.0 & 1000 V Accuracy: ±0.05% of nominal voltage Arms Measurement range: 0.0 & 4000 mV x clamp scaling Accuracy: ±5% ± 5 counts Watt Measurement range: Depends on clamp scaling and voltage Accuracy: ±5% ± n x 2% or reading ± 10 counts DC voltage |
Transient Capture | Volts Measurement range: ±6000 V |
Autotrend Recording | Sampling: 5 readings/sec continuous sampling per channel |
Safety | EN61010-1 (2nd edition) pollution degree 2; 1000 V |
Operating temperature | 0 ºC to +50 ºC |
Battery Life | Rechargeable NiMH pack (installed): >7 hours |
Dimension
US | Metric | |
Dimensions | - | 256 x 169 x 64 mm |
Weight
US | Metric | |
Weight | - | 1.1 kg |