FLUKE 435 POWER QUALITY
Fluke

FLUKE 435 POWER QUALITY

Pine Item #54579

Pinpoint power quality problems faster, safer and in greater detail with the Fluke 435 power quality analyzer. These three-phase power quality meters help you locate, predict, prevent and troubleshoot problems in power distribution systems. These easy-to-use power quality tools are a  “must have ” for any person who maintains or troubleshoots three phase power. The new IEC Class A standards for flicker and power quality are built right in to take the guess work out of power monitoring.

Features:

\r

Automatic transient mode: Captures 200 kHz waveform data on all phases simultaneously: Up to 6 kV\r

Highest safety rating in the industry: 600 V Cat IV/1000 V CAT III rated for use at the service entrance\r

Troubleshoot real-time: Analyze the trends using the cursors and zoom tools even while background recording continues

Applications:

\r

Automatic transient mode: Captures 200 kHz waveform data on all phases simultaneously: Up to 6 kV\r

Highest safety rating in the industry: 600 V Cat IV/1000 V CAT III rated for use at the service entrance\r

Troubleshoot real-time: Analyze the trends using the cursors and zoom tools even while background recording continues

Quantity must be 1 or more
Email for Quote

Specifications

Technical Specifications

Volt/Amps/HertzVrms (AC + DC) Measurement range: 1 ... 1000 V Accuracy: 0.1% of Vnom Vpeak Measurement range: 1 ... 1400 V Accuracy: 5% of Vnom Crest factor voltage Measurement range: 1.0 ... > 2.8 Accuracy: ±5% Arms (AC + DC)
InputsNumber: 4 voltage and current (3 phases + neutral) Maximum voltage: 1000 Vrms (6 kV peak)
Dips and swellsVrms (AC+DC) ² Measurement range: 0.0% & 100% of Vnom Accuracy: ±0.2% of nominal voltage Arms (AC+DC) ²
HarmonicsMeasurement range: DC 1..50; (Off 1..49) Vrms Measurement range: 0.0 & 1000 V Accuracy: ±0.05% of nominal voltage Arms Measurement range: 0.0 & 4000 mV x clamp scaling Accuracy: ±5% ± 5 counts Watt Measurement range: Depends on clamp scaling and voltage Accuracy: ±5% ± n x 2% or reading ± 10 counts DC voltage
Transient CaptureVolts Measurement range: ±6000 V
Autotrend RecordingSampling: 5 readings/sec continuous sampling per channel
SafetyEN61010-1 (2nd edition) pollution degree 2; 1000 V
Operating temperature0 ºC to +50 ºC
Battery LifeRechargeable NiMH pack (installed): >7 hours

Dimension

USMetric
Dimensions-256 x 169 x 64 mm

Weight

USMetric
Weight-1.1 kg